|             |Print Print
International site

Turbine water, cooling water and drinking water at power plant

Reference ID: 045000
Industry: Heat and power plants
Application: Boiler water, Cooling Water

EUROWATER has supplied the power plant with a.o. pressure filter, activated carbon filter, UV-disinfection unit, reverse osmosis units, cartridge filter, electrodeionization unit, and mixed-bed unit. 

Technical data

  • Flow, turbine water: 1.5 m³/h
  • Flow, cooling water: 7.5 m³/h
  • Flow, drinking water: 2.0 m³/h

Units in plant

  • Pressure filter NSB 200 with blower and rinse pump
  • Activated carbon filter ACH 1801
  • UV-disinfection unit Aquada 7
  • Dosing of antiscalant
  • Bag filter
  • Reverse osmosis unit RO 03-6
  • Dosing of NaOH
  • Cartridge filter
  • Reverse osmosis unit RO 01-5
  • Electrodeionization unit EDI 1-1100i
  • Cartridge filter as resin trap
  • Mixed-bed as back-up EUREX 601
  • PLC control panel with touch screen